Analisis Perbaikan Drop Tegangan dengan Metode Pecah Beban pada Penyulang GNAP PT. PLN (Persero) ULP Plered
Abstract
The electricity demand continues to increase every year in line with advancing technology and society's dependence on electricity supply. The society's reliance on electricity drives the improvement of power quality by PLN, one of which is the enhancement of voltage quality. At PT. PLN (Persero) Unit Layanan Pelanggan (ULP) Plered, there is a distribution feeder with an end voltage that is still below the standard. In this study, an analysis of the system related to the improvement of voltage drop on the GNAP distribution feeder was conducted with the assistance of ETAP simulation. The voltage drop improvement was carried out using the load splitting method, which involves redistributing a portion of the load to another feeder. The obtained results show that the voltage drop on the GNAP feeder decreased from the initial 1.19 kV to 0.84 kV during daytime load and from 1.24 kV to 0.90 kV during nighttime load. The voltage loss also experienced a decrease from the initial 5.95% to 4.18% during daytime load and from 6.20% to 4.51% during nighttime load.
References
[2] PT PLN (Persero), Peraturan Direksi Nomor 76 tahun 2020 tentang Organisasi dan Tata Kerja PT PLN (Persero), Jakarta, 2020.
[3] PT PLN (Persero), Laporan Teknik Bulan Januari ULP Plered, Purwakarta, 2023.
[4] Y. Heryadi, Interviewee, Perkembangan Beban Pada ULP Plered. [Wawancara]. 02 Februari 2023.
[5] R. T. Tanto dan I. Alfi, “Optimalisasi Pengaturan Tegangan Menggunakan Tap Changer,” Universitas Teknologi Yogyakarta.
[6] J. Asrul dan Firmansyah, “Reconnecting Sambungan Rumah (SR) Pada Gardu 079 Sovia Untuk Mengurangi Losses di PT. PLN (Persero) Rayon Bukittinggi (Menggunakan Aplikasi Jaringan Syaraf Tiruan),” Politeknik Negeri Padang.
[7] Y. A. Deavy, A. B. Fakhri dan M. Putri, “Analisis Perbaikan Jatuh Tegangan Dengan Uprating Penghantar Di NR.06 Menggunakan Software ETAP,” Politeknik Negeri Medan.
[8] Hamimi, M. I. Chaniago dan H. Widodo, “Analisis Drop Tegangan Listrik Menggunakan ETAP Pada Penyulang Utari PT. PLN (Persero) Unit Layanan Pelanggan Bandarjaya,” Universitas Muhamadiyah Lampung.
[9] PT PLN (Persero), Laporan Beban Harian Bulan Januari UP3 Purwakarta, Purwakarta, 2023.
[10] Kelompok Pembakuan Bidang Distribusi dan Kelompok Kerja Konstruksi Distribusi, SPLN 72: 1987 – Spesifikasi desain untuk Jaringan Tegangan, 1987.
[11] W. B. E. P. Daya, Asmar dan T. Hendrawan, “Analisa Pecah Beban Penyulang KB5 Di PLN Rayon Koba Untuk Perbaikan Tegangan Dan Susut,” Universitas Bangka Belitung.
[12] I. Amu, Y. Mohamad dan A. I. Tolago, “Kajian Kelayakan Operasi Pecah Beban Penyulang Beta (SJ-2) Untuk Kehandalan Sistem Kelistrikan Kota Bitung,” Universitas Negeri Gorontalo.
[13] B. Isnanto, M. Jumnahdi dan M. Y. Puriza, “Studi Rekonfigurasi Jaringan Distribusi di Penyulang Dendang PLN UP3 Belitung,” Universitas Bangka.
[14] D. Suswanto, Sistem Distribusi Tenaga Listrik, 2009.
[15] Kelompok Kerja Standar Konstruksi Distribusi Jaringan Tenaga Listrik dan Pusat Penelitian Sains dan Teknologi Universitas Indonesia, Buku 5 – Standar Konstruksi Jaringan Tegangan Menengah Tenaga Listrik, 2010.
[16] W. H. Kersting, Distribution System Modeling and Analysis – Third Edition, 2012.
[17] A. Supriyadi, Analisa Aliran Daya Pada Sistem Tenaga Listrik Menggunakan Software ETAP 12.6, Forum Teknologi.